Heat transfer compounds

More Information

Heat transfer compounds overview

Whether

  • bonding tracer tubing to long piping runs
  • irregular surfaces (valves and pumps) or
  • tank walls,

there is a product specifically designed for every trace heating application.

 

Take a look at our heat transfer compound selectrion matrix below.

 

View Products! Browse our catalogues & add products of interest to your "enquiry list" or
contact us to discuss your requirements.

Product selection chart

Product

Standard T-3

T-63

T-80

T-85

T-802

NH Nonhardening

SnapTrace*

Standard Use Provide an efficient thermal connection between tracer and process equipment for high temperature maintenance or high exposure temperatures. Also used with ChannelTrace system featuring TFK galvanized steel channel. Suitable for use in areas of extreme moisture and/or corrosive environments with low to medium exposure temperatures. These products are particularly suited for valves and similar equipment. Self-curing - no heat required. Suitable for use in areas of extreme moisture and/or corrosive environments. Used where periodic disassembly is necessary or for plate-type heating coils. Preformed compound designed for rapid, consistent installation under TFK channel on straight runs of piping.
Maximum Exposure Temperature 700°F (371°C) 1,250°F (677°C) 325°F (163°C) 375°F (190°C) 275°F (135°C) 375°F
(190°C)
406°F (208°C)
Minimum Exposure Temperature -320°F (-196°C) -320°F
(-196°C)
-320°F
(-196°C)
-320°F
(-196°C)
-100°F
(-73°C)
Minimum Installation Temperature 32°F (0°C) Ambient 0°F (-18°C)
Product 10°F (-12°C)
Ambient 32°F (0°C)
Product 70°F (21°C)
32°F
(0°C)
Ambient 32°F (0°C)
Product •200°F
(93°C)
10°F
(-12°C)
Heat Transfer Coefficient, U Tracer to pipe wall
20-40 Btu/hr·°F·ft²
(114-227 w/m²·°C)
Tracer to pipe wall
20-40 Btu/hr·°F·ft²
(114-227 w/m²·°C)
Tracer to pipe wall
20-40 Btu/hr·°F·ft²
(114-227 w/m²·°C)
Heater to tank wall
20-40 Btu/hr·°F·ft²
(114-227 w/m²·°C)
Tracer to pipe wall
20-40 Btu/hr·°F·ft²
(114-227 w/m²·°C)
Bond Shear150 lbs/in²
(1.034 kPa)
1,000-1,800 lbs/in²
(6,895-12,411 kPa)
1,000 lbs/in²
(6,895 kPa)
N/A100-150 lbs/in²
(689-1,034 kPa)
Start-Up TechniqueNo special curing procedure required if installed with TFK channel; otherwise, compounds must be cured for 4-12 hours at 160°F to 212°F (71°C to 100°C).No special curing procedure required. T-80 and T-85 cure in 4-12 hours at 212°F to 325°F (100°C to 163°C).No special curing procedure required.No special curing procedure required.Must be heated to 200°F (93°C) to promote surface wetting and curing.
Method of InstallationHand trowel or use with TFK channel (Carbon steel tube tracers are not recommended)
(ALP primer must be applied to aluminum surfaces)
Manual or air-powered cartridge gun (Electrically heated barrel available)Hand trowelHand trowel on plate-type heating coilsUse with TFK channel
Water SolubleYesNoNoNoNo
Electrical Resistivity0.267 ohm/inch
(0.105 ohm/cm)
3.3 ohms/inch
(1.299 ohms/cm)
146 ohms/inch
(57 ohms/cm)
146 ohms/inch
(57 ohms/cm)
320 ohms/inch
(126 ohms/cm)
146 ohms/inch
(57 ohms/cm)
Shelf Life1 year90 days for 1/10-gallon (0.379 liter) cartridges,
30 days for 1 and 5-gallon (3.79 and 18.93-liter) cans,
(Shelf life can be extended up to 1 year is material is stored below 40°F [4°C]).
1 Year
(unmixed)
IndefiniteIndefinite
Container Size Available1-gal (3.79 l) cans
5-gal (18.93 l) cans
1/10-gal
(0.379 l) cartridges
1 and 5-gal
(3.79 l and 18.93 l) cans
1-quart
(0.946 l) cans
1-gal
(3.79 -) cans
1-quart (0.946 l) cans 1-gal (3.79 l) cans
5-gal (18.93 l) cans
4-foot (1.22-m) lengths
25 sections per box
Weight per Unit14 lbs
(6.4 kg)/gal
13 lbs
(5.9 kg)/gal
13 lbs
(5.9 kg)/gal
13 lbs
(5.9 kg)/gal
0.33 lb/ft
(0.05 kg/m)
More info & get a quote >> >> >> >> >> >> >>

*SnapTrace heat transfer compounds must be heated to a temperature of at least 93°C (200°F) to promote surface wetting and curing.

SnapTrace

Preformed Flexible Heat Tracing Compound

Snap TraceSnapTrace is a preformed flexible heat transfer compound designed for straight piping runs, 1-1/2 inches (38 mm) and larger.

SnapTrace includes TFK galvanized channel, providing mechanical and weather protection.

A single SnapTrace has the equivalent heat output of 3 to 6 bare tracers, because its eliminating air gaps associated with bare tracers. It is available in 4' long sections to fit on every piping without any problems.


Advantages of Preformed Flexible Heat Tracing Compound:

  • Increased heat transfer (3-6 times better than bare tracers)
  • Easy, fast installation (snap-on)
  • No curing procedure required
  • Factory-formed to fit tracer and pipe (1.22m sections)
  • No surface preparation required
  • Non-soluble in water

Contact us to discuss your requirements